welcome To Shijiazhuang Dekun Technology Co., Ltd. Official website!
Language: 中文版 ∷  英文版

DK1100 series

  • DK1100 single channel remote voltage current and single channel DA data acquisition module
  • DK1100 single channel remote voltage current and single channel DA data acquisition module

DK1100 single channel remote voltage current and single channel DA data acquisition module

  • DK1100 remote data acquisition module is an intelligent module which integrates signal acquisition, transmission, DA output and communication. It has the characteristics of high measurement accuracy, good stability, modular structure, flexible configuration, good linearity and strong anti-interference ability.

  • Online orders

Product features

Support a variety of common industrial standard signal input;

The output mode is optional, which supports two modes of measuring and sending and communicating DA.

Compact size, easy installation, standard 35mm guide rail installation;

DC24V/AC220V power supply optional.

Signal input, power supply, variable output three terminal isolation, isolation voltage 1500V AC.


input

Dc gear 11

0-(-5-5A), 1-(-1-1A), 2-(-100-100mA), 3-(-75-75mV), 4-(4-20mA) 5-(0-20mA) 6-(0-10mA) 7-(-500-500V) 8-(-100-100V), 9-(-10-10V) 10-(-1-1V)

7 exchanges

11- (0-5A) 12- (0-1A) 13- (0-100mA), 14- (0-500V) 15- (0-100V), 16- (0-100V), 17(0-1V)


output

0-5, 1-5V, 0-10V, 0-10mA, 0-20mA, 4-20mA


communication

Adopt the international standard photoelectric isolation MODBUS RTU communication mode.


Other detailed parameters

Comprehensive parameters

Comprehensive measurement accuracy

0.3%FS

Sampling speed

2KSPS

Transmission precision

16 bits

DA speed

10M SPS

Isolation voltage

Input, output and power 1500V AC 1 minutes between the three parties.

temperature drift

50ppm

electromagnetic compatibility

GB/T 18268 (IEC61326-1)

Use of the environment

Ambient temperature: 0~50 C; relative humidity: less than 85%RH; avoid strong corrosive gases.

Power Supply

DC24V/AC220V

Power waste

Power consumption is less than 2.4W

structure

35mm DIN guide rail installation

Selection size

Width * height * depth: 22.5*100*112mm


Example selection

1. customers need to exchange 0-5A current signal input; communication given DA, output is 4-20MA current signal;

Select 220V power supply.

The selection is as follows:

DK1100-AC-0A5-4MA20-AC220V

2. customers need DC -500V-500V voltage signal input; communication given DA, output 0-10V voltage signal;

The site is conveniently supplied with 24V power supply.

The selection is as follows:

DK1100-DC-500V-0V10-DC24V