welcome To Shijiazhuang Dekun Technology Co., Ltd. Official website!
Language: 中文版 ∷  英文版

DK6200 series

  • DK62H8A single phase true effective value J AC multifunction voltage and current power meter

DK62H8A single phase true effective value J AC multifunction voltage and current power meter

  • DK62H8 single phase true RMS multifunction table, including DK62H8A and DK62H8D two. It can be used as single phase AC and DC measurement and transmission applications. The product has two power conversion functions. The installation of standard tray cabinet is adopted. The product can measure AC, DC power, voltage and current value. AC measurement uses true RMS measurement. DC measurement is very accurate. The product also has standard MODBUS RTU communication. This product also has the function of display and keystroke operation. Realize specialization and high precision functional measurement. DC measurement can be widely applied to wind power, photovoltaic and new energy application neighborhood. The first instrument in China has AC and DC high accuracy and true value measurement.

  • Online orders


Product features


It supports 2 way transmit output.

Support two DI detection;

Support communication function;

Voltage compatible AC and DC multi scale input, and can be configured with voltage transformer to expand the range.

Current compatible AC and DC multi range

The input can be configured with current transformer to expand the range.

Digital filtering can effectively eliminate interference and eliminate non critical jumps.

It can realize the 2 way relay alarm.

True RMS measure voltage, current and power, and measure electric energy.

input

Voltage range: AC500V, AC100V

Current range: AC5A, AC1A, DC5V

output

4-20MA

1-5V

0-20mA

0-10mA

0-10V

0-5V

communication

Photoelectric isolation RS-485 communication interface

alarm
It can realize the 2 way relay alarm.

Other detailed parameters


Model: DK62H8A (AC)

Measurement accuracy: + 0.5% (+ 0.3%).

Corresponding frequency: 40Hz~70Hz (AC)

Working power supply: AC220V

Working environment: 0 ~ + 50 C; less than 85%RH

Relay contact capacity: AC220V/5A

Relay contact life: 105 times

Variable output accuracy: 16 bits + 0.2%

Selection size

Outline size: 96mm*48mm*112mm

Opening size: 92mm*45mm

Example selection

Example: Users need to measure single-phase AC voltage of 0-380V, rated current of 50A. They need to alarm when the measured voltage is higher than 400V, and when the measured voltage is lower than 300V. The power supply of the system is AC220V. It is necessary to change the data voltage 0~380V and current 0~50A to 4-20MA, and analog signals are sent to remote transmission.

Instrument selection: DK62H8A-AC500v-AC5A-R-R-V4MA20-I4MA20-S